Feature |
•Measure single phase active power with high-precision. |
•Provide LED display and local data query. |
•Programmable current and voltage transformation ratio. |
•Support RS-485 communications and Modbus-RTU protocol. |
•Support switch input, switch output and analog output. |
•Power supply:AC 22OV; AC/DC 85~265V; AC380V; DC 48V; DC 24V; DC 12V |
•There are various choices of dimensions to meet the requirements of different electrical circuit enclosure. |
Technical Index |
Accuracy Measurement |
current | class 0.5 |
Voltage | class 0.5 |
Input Measurement |
Wiring | single-phase |
Rated current | AC 1A,5A; DC75mA, 20mA, 4-20mA |
Rated voltage | AC 100V, 220V, 380V, 1000V; DC 2V, 20V, 200V, 1000V |
Overload | Voltage:Sustained:1.2times;Instantaneous:2times/1s |
| Current:Sustained: 1.2 times; Instantaneous: 10 times/ 5s |
Power consumption | ≤2VA |
Impedance | Voltage: >300KΩ , Current: <20mΩ |
Frequency | 45~65Hz |
Power supply |
Working range | AC 22OV; AC/DC 85~265V; AC380V; DC 48V; DC 24V; DC 12V |
Power consumption | <4VA |
Functional Module |
Communication interface | 1 loop RS-485 Communication, MODBUS-RTU protocol |
| Baud rate: 2400 ~ 19200bps, Default: 2400bps |
Switching value input | 4 loops switching value input, dry joint |
Switching value output | 3 loops relay output, capability: AC 250V/5A,DC 30V/5A |
Transmission output | 3 loops analog output: 0/4~20 mA or 0~5/10 V |
Environment |
Operational environment | -25°C~+55°C |
Storage environment | -25°C~ +70°C |
Relative humidity | ≤93 %,in the place without corrosive gas |
Height above sea level | ≤2500m |
Outline Dimension |
External Dimension( mm ) | 96×48mm; |
Cutout Dimension( mm ) | 92×45mm; |